14. Entry/exit
delay 1 with
group bypass
A trip starts entry delay 1. This zone bypasses
when the group bypass command is entered at the
keypad. The lack of a trip during exit delay enables
the automatic bypass or instant mode if
programmed.
15. Interior
follower with
group bypass
This zone is instant when the system is armed and
no entry or exit delays are being timed. It is delayed
during entry/exit delay times. This zone bypasses
when the group bypass command is entered at the
keypad. This zone automatically bypasses if
enabled in segment 1.
16. Instant with
group bypass
This zone creates an instant alarm whenever it is
tripped and the armed LED is on. This zone
bypasses when the group bypass command is
entered at the keypad.
17. Entry/exit
delay 1 with
tamper
A trip starts entry delay 1. The lack of a trip during
exit delay enables the automatic bypass or instant
mode if programmed. This zone type is used to
enable the tamper on a wireless transmitter.
18. Interior
follower with
tamper and
autobypass
This zone is instant when the system is armed and
no entry or exit delay is being timed. It is delayed
during entry and exit delay times. This zone
automatically bypasses if enabled in segment 1.
This zone type is used to enable the tamper on a
wireless transmitter.
19 Instant with
tamper
This zone creates an instant alarm whenever it is
tripped and the armed LED is on. This zone type is
used to enable the tamper on a wireless
transmitter.
20. Entry/exit
delay 2 with
tamper
A trip starts entry delay 2. The lack of a trip during
exit delay enables the automatic bypass or instant
mode if programmed. This zone type is used to
enable the tamper on a wireless transmitter.
21. Gas
detection
This zone creates an instant alarm regardless of
the armed state of the control panel. It displays on
the keypad and activates the keypad sounder.
22. Low
temperature
detection
This zone creates an instant silent alarm regardless
of the armed state of the control panel. It displays
on the keypad and activates the keypad sounder.
23. High
temperature
detection
This zone creates an instant silent alarm regardless
of the armed state of the control panel. It displays
on the keypad and activates the keypad sounder.
24. Manual fire
This zone illuminates the fire LED and sounds the
temporal siren each time the zone is shorted. It
also flashes (rapidly) the fire LED, indicating a
problem if the zone is open.
25. Chime only
This zone creates no alarm regardless of the
armed state of the control panel. It chimes anytime
it is faulted and displays on the keypad. Local only.
26. Interior
follower delay 2
This zone is instant when the system is armed and
no entry or exit delay is being timed. It is delayed 2
times during entry and exit. This zone automatically
bypasses if enabled in segment 1.
27. Interior
follower force
armable
This zone is instant when the system is armed and
no entry or exit delay is being timed. It is delayed 1
time during entry and exit. This zone automatically
bypasses if enabled in segment 1.
28. Entry/exit
force armable
delay 2
A trip starts entry delay 2. The lack of a trip during
exit delay enables the automatic bypass or instant
mode if programmed.
29. Interior
follower with
activity
supervision
This zone is instant when the system is armed and
no entry or exit delay is being timed. It is delayed
during entry and exit delay times. It sends a report
if the zone activity time is reached without a change
of state. This zone automatically bypasses if
enabled in segment 1.
30. Entry/exit
with activity
supervision
A trip starts entry delay 1. It sends a report if the
zone activity time is reached without a change of
state. The lack of a trip during exit delay enables
the automatic bypass or instant mode if
programmed.
Underwriters laboratories information
The NetworX NX-6V2 holds the following listings from
Underwriters Laboratories (US and Canadian)
UL365
Police station connected burglar alarms.
UL609,
CAN/ULC-S303-
M91
Mercantile, police station connect with basic line
security requires NX-003-C enclosure
UL985,
CAN/ULC-S545-
M89
Household fire
UL1023, ORD-
C1023-1974
Household burglary
UL1610
Central station burglar alarm unit
UL1635
Digital alarm communicator system units
UL1637
Home health care signaling
When installing an NX-6V2 in compliance with Underwriters
Laboratories, the following instructions must be observed:
•
Initiating and indicating devices must be rated at 11.5 to
12.4 VDC residential, 12.0 VDC commercial.
•
Force arming and auto arming must not be enabled.
•
For residential fire applications, the indicating devices
shall be a Wheelock 34T-12 or equivalent.
• The
listen in feature shall not be enabled.
•
The siren/bell test must be enabled. The auxiliary outputs
controlling the audible device require a minimum cutoff
time of 15 minutes for commercial burglary, four minutes
for residential applications, or 30 minutes for commercial
burglary for Canada.
•
For residential fire installations, the dynamic battery test
time cannot exceed four hours.
•
Ringback must be enabled on UL commercial burglary
installations.
•
On commercial burglary installations, the fire initiating
circuits must not be connected.
•
The entry guard feature must be disabled.
•
Group bypassing must be disabled.
•
Delay before dial seizure must be set to 0.