Troubleshooting – FloAire NSA User Manual
Page 15
![background image](/manuals/676136/15/background.png)
15
Troubleshooting
The following table lists causes and corrective actions for possible problems with the fan units. Review
this list prior to consulting manufacturer.
Troubleshooting Chart
Problem
Potential Cause
Corrective Action
Fan Inoperative
Blown fuse or open circuit breaker
Replace fuse or reset circuit
breaker and check amps
Disconnect switch in “Off” position
Turn to “On” position
Motor wired incorrectly
Check motor wiring to wiring
diagram located on fan motor
Broken fan belt
Replace belt
Motor starter overloaded
Reset starter and check amps
Motor Overload
Fan rotating in the wrong direction
Be sure fan is rotating in the
direction shown on rotation label
Fan speed is too high
Reduce fan RPM
Motor wired incorrectly
Check motor wiring to wiring
diagram located on fan motor
Overload in starter set too low
Set overload to motor FLA value
Motor HP too low
Determine if HP is sufficient for
job
Duct static pressure lower than
design
Reduce fan RPM
Insufficient Airflow
Fan rotating in the wrong direction
Be sure fan is rotating in the
direction shown on rotation label
Poor outlet conditions
There should be a straight clear
duct at the outlet
Intake damper not fully open
Inspect damper linkage and
replace damper motor if needed
Duct static pressure higher than
design
Improve ductwork to eliminate or
reduce duct losses
Blower speed too low
Increase fan RPM. Do not
overload motor
Supply grills or registers closed
Open and adjust
Dirty or clogged filters
Clean and/or replace
Belt slippage
Adjust belt tension
Excessive Airflow
Blower speed to high
Reduce fan RPM
Filters not installed
Install filters
Duct static pressure lower than
design
Reduce fan RPM
Excessive Vibration and Noise
Misaligned pulleys
Align pulleys
Damaged or unbalanced wheel
Replace wheel
Fan is operating in the unstable
region of the fan curve
Refer to performance curve for
fan
Bearings need lubrication or
replacement
Lubricate or replace
Fan speed is too high
Reduce fan RPM
Belts too loose, worn or oily
Inspect and replace if needed