Intrepid 1640 woodburning stove, Alcove installations, Construction requirements – Vermont Casting 1640 User Manual

Page 13

background image

13

Intrepid 1640 Woodburning Stove

30000830

Alcove Installations

Because of their restricted air flow and heat retention
characteristics, specific construction requirements and
special clearances apply to installations into alcoves.
No stove or chimney connector heat shields are used
in alcove installations.

ALCOVE INSTALLATION OF THE INTREPID II IS
NOT PERMITTED IN CANADA.

Construction Requirements

The following illustrations show noncombustible ceiling
framing and maximum and minimum permitted dimen-
sions for alcove construction.

36"

Max.

48" Min.

Fig. 22 Alcove floor plan. Sheetrock on front face butts to
Durock® (or equivalent) alcove lining.

Use recommended
floor protection

7/16" Durock®
(or equivalent)
spaced 1" off
wood studs on
non-combustible
spacers

ST502

I N T R E P I D I I

Metal
stud

A: This area, from
62" to 65" must be
covered with a
non-combustible
material

7/16" Durock®

(or equivalent)

Fig. 23 Alcove side section.

Joist shield
(supplied by
chimney
manufacturer)

1" air gaps,
top and
bottom, on
both sides
and back
wall

B: Combustible
facing may
overlap metal
studs by only 1"

B

A

ST503

Fig. 24 Cutaway perspective of alcove installation.

ST504

24"

14

¹⁄₄

"

48" Min.

11"

Min.

36"

Min.

Metal studs
support 7/16"
Durock® (or
equivalent)
ceiling

Fig. 25 Reflected ceiling plan.

Existing combustible
framing

ST505

65"

62" Min.

to Alcove

Ceiling

Ceiling support
package
extends 2"
below Durock®
(or equivalent)
ceiling

1" air gap,
top and
bottom,
on both
sides and
back wall

Fig. 26 Front view: 65" minimum clearance from hearth to
combustibles on front face. Combustible facing may overlap
metal studs by only 1". It should not extend below the height
of the non-combustible ceiling.

ST506