MAC 10 LE-AC SERVICE MANUAL

6 E

G

A

P

Figure 2 – Foam Prefilter Cleaning

3 SERVICE: Cleaning the MAC 10 LE-AC Prefilter (G4 Pleated

Prefilter)

WARNING!

Disconnect the unit from the electrical power source before attempting any

service.

Tools Required:

None

Note: To keep the filter in top operating condition replacing the pleated prefilter is

recommended every twelve months or sooner.

Step 1. To gain access to the prefilter, remove the ceiling panel next to the unit, if

applicable.

Step 2. Switch the ON-OFF switch to the off position.

Step 3. Remove the prefilter from the snap-in frame. The beverage frame has slots

that have to be depressed to release the filter from the prefilter housing (See

Figure 3)

Step 4. After removing the new G4 pleated prefilter from the box, remove the die cut

slots from the beverage board frame and install on prefilter bracket.

Step 5. Reassemble by reversing the above steps.

Figure 3 – G4 Prefilter Replacement

ON/OFF Switch