WIRE ANO MOUNT THERMOSTAT (continued)
□
Recheck for level positioning, and firmly
tighten both mounting screws.
□
If installing CTSOA or CT51A, make sure
you have the current (anticipator setting)
for your system Ttiis is the number you wrote in
the box in step 3. If you were unable to find the
current draw for step 3, this information can be
found printed on the primary control at the
iumace. The primary control is usually a gas
vatve. zone valve, or a relay or burner control box
with the thermostat wires connected to it. For
electric heat, you need to add tine f. n relay
current, usually 0 2 to 0.4 A.
OIL BURHEh CONTROL
CHECKOUT THE
THERMOSTAT
CAUTtON
To prevent possible com
pressor damage, do not
operate air conditioning if
outdoor temperature is
below 50° F [10° C], Once
the air conditioner is off.
do not turn it on for S
minutes; this action will
prevent
compressor
damage.
□
On the CT51A, the system
switch controls as follows:
HEAT—heating system only
operates.
OFF—heating and air condi
tioning systems are dis
connected
COOL—air conditioning sys
tem only operates.
The tan switch controls as
follows:
AUTO—Ian operates wheri
heating or air conditioning
system operates.
ON—fan operates continu
ously.
NOTE: In the following instruc
tion. disregard healing or air
conditioning directions if not
applicable to your system.
П
Turn on power to the
heating/air conditioning
system,
□
Observe system operation
for at least one cycle on
both heating and air conditioning.
To observe;
□
Place the system switch
at HEAT position and fan
switch at AUTO. Move the temper
ature setting lever t0° F ¡6° C]
above room temperature. The
heatirig equipment should turn
on. A short warm-up period may
be required before the system
fan turns on,
□
Place system switch at
COOL position and move
temperature setting lever 10° F
[6° C] below room temperature.
The air conditioning equipment
should turn on and the system
fan should turn on.
NOTE; Some systems have a time
delay that can prevent opera
tion up to 5 minutes.
□
Turn the fan switch to ON.
The system fan should turn
on. and operate continuously.
The system blower should con
tinue to operate at any system
switch or thermostat setting.
□
On the CT50A or CT51A, set heat
anticipator indicator at rating printed on
primary control.
□ Press the thermostat cover firmly onto the
mounting clips
THERMOSTAT
SETTING
□
On CT51A, place the sys
tem and fan switches at
the desired settings for operation.
□
On all models, move the
temperature setting lever
to the desired temperature com
fort level
CAUTION
If your anticipator is set too low, it may
burn out.
Shorting out your valve or control could
cause your anticipator to bum out.