Installation Instructions (cont’d)

Venting (cont’d)

All vent gases must be completely vented to the outdoors of the
structure (dwelling). Install only the draft hood provided with

the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

TO

CHIMNEY

MIN. % INCH

RISE PER LINEAR

FOOT

VENT PIPE INSTALLATION

Gas Piping

AWARNING

Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed

14 inches water column Vi pound per square inch (3.5kPa).

The minimum inlet gas pressure listed on the model rating

plate is for the purpose of input adjustment

_____________ AWARNING

If the gas control valve is subjected to pressures exceeding

pound per square inch (3.51^), the damage to the gas con­
trol valve could result in a fire or explosion from leaking gas.

There must be a minimum of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear­

ance between single wall vent pipe and combustible material
with mortar mix, cement, of other noncombustibk substance.

For other than single wall, follow vent pipe manufacturer’s clear­
ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix

cement.

AWARNING

Failure to have required clearances between vent pipins and

combustible material will result in a fire hazard.

AWARNING

Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases vriiich could cause deadly asphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes, bleach, and process chemicals are
typical compounds which are potentially corrosive.

AWARNING

If the main gas tine shutoff serving all gas appliances b used,

abo turn “OFF" the gas at each appliance. Lem all gas appli­

ances shut off until the water heat№ installation is complete.

A gas line of sufficient size must be tun to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI

Z223.1, also referred to as NFPA54 and the gas company concern­

ing pipe size.

There must be;
• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

• A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

Standard Models are for ^stallation up to 3,300 feet above sea
level.
High Altitude Models are for installation from 3.300 to 5,500

feet above sea level.
If a standard model is installed above 3,300 feet or a high altitude

model is installed above 5,500 feet, the Input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.

Contact your local Sears Service Center or gas utility for further

information.

AWARNING

The appliance and its gas connection must be teak tested

before placing die appliance in operation.

14