beautypg.com

Caution, Temperature-pressure relief valve, Adanger – Kenmore 153.31242 User Manual

Page 11: Temperature-pressure relief valve 11, Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

block the discharge opening or hinder access to the manual
relief lever (Figure 9). Ensure a discharge pipe is installed
into the T&P valve discharge opening per the instructions in
this manual.

4. Locate the hot water (outlet) & cold water (inlet) pipes to the

water heater.

5. Locate the slit running the length of a section of pipe

insulation.

6. Spread the slit open and slip the insulation over the cold

water (inlet) pipe. Apply gentle pressure along the length of
the insulation to ensure that it is fully seated around the pipe.
Also, ensure that the base of the insulation is flush with the
water heater. Once seated, secure the insulation with duct
tape, electrical tape, or equivalent.

7. Repeat steps 5 and 6 for the hot water (outlet) pipe.

8. Add additional sections of pipe insulation as needed.

The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water
heater (150 psi = 1,035 kPa) and a discharge capacity not less
than the water heater input rate as shown on the model rating
plate. (For electric heaters, watts x 3.412 equals Btu/hr input
rate)

For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly

into the fitting of the water heater designed for the relief valve.
Position the valve downward and provide tubing so that any

discharge will exit only within 6 inches (153 mm) above, or at any
distance below the structural floor. Be certain that no contact is

made with any live electrical part. The discharge opening must
not be blocked or reduced in size under any circumstances.
Excessive length, over 30 feet (9.14 m), or use of more than

four elbows can cause restriction and reduce the discharge

capacity of the valve.

T&P Relief Valve Insulation

CAUTION

Temperature-Pressure Relief Valve

A

warning

Explosion Hazard

Temperature-pressure relief valve
must comply with ANSI Z21.22
CSA 4.4 andASMEcode.

Properly sized temperature-relief

valve must be installed in opening

provided.

Can result in overheating and
excessive tank pressure.

Can cause serious injury or death.

This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed
equipment of materials as meeting the requirements for Relief
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4,
and the code requirements of ASME.

If replaced, the valve must meet the requirements of local codes,

but not less than a combination temperature and pressure relief
valve certified as indicated in the above paragraph.

Water Damage Hazard

Temperature-pressure relief valve discharge

pipe must terminate at adequate drain.

No valve or other obstruction is to be placed between the relief

valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided. To prevent bodily

injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances

demand. If the discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.

• Shall be of material listed for hot water distribution.

• Shall be installed so as to allow complete drainage of both the

temperature-pressure relief valve, and the discharge pipe.

• Shall terminate a maximum of six inches above a floor drain or

external to the building. In cold climates, it is recommended
that the discharge pipe be terminated at an adequate drain

inside the building.

• Shall not have any valve between the relief valve and tank.

ADANGER

Water temperature over 125°F

(52°C) can cause severe burns
instantly resulting in severe injury
or death.

Children, the elderly, and the
physically or mentally disabled
are at highest riskfor scald injury.

Feel water before bathing or

showering.

Temperature limiting valves are

available.

Read instruction manual for safe

temperature setting.

11