beautypg.com

Installation instructions (cont’d), Venting (cont’d), Gas piping – Kenmore 153.33439 User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Installation Instructions (cont’d)

Venting (cont’d)

All vent gases must be completely vented to the outdoors of the

structure (dwelling). Install only the draft hood provided with
the new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.

VENT PIPE INSTALLATION

Gas Piping

AWARNING

Make sure the gas supplied is the same type listed on the
mod^ rating plate. The inlet gas pressure must not exceed

10.5 in. voter column (2.6kPa) for natural gas or 13 in. water

column (3.2kPa) for propane (LP.) gas. The minimum inlet

gas pre^re listed on the moM rating plate is for the pur­

pose of input adjustment.

__________ AWARNING_________________ ^

H the gas control valve is subjected to pressures exceeding

'A

pound per square inch (3.5k^), the dam^ to the gas con­

trol vaho could result in a fire or explosion ^m leaking gas.

There must be a minimum of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear­
ance oetween single wall vent pipe and combustible material
with mortar mix, cement, or other noncombustible substance.
For other than single wall, follow vent pipe manufteturer’s clear­
ance speciGcations. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.

AWARNING

Failure to have required clearances between vent piping and
combustible material will result In afire hazard.

AWARNING

Be sure vent pipe Is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chioride, waxes, bleadi, and process chemicals are
typical compounds which are potentially corrosive.

AWARNING_________________ ^

K the main gas line shutoff serving all gas apfriiances is used,
also turn “OFP’ ^ gas at each a^iance. Lem all gas appli­
ances shut off until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gas company concern­
ing pipe size.

There must be:

• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment tr^) ahead of the gas control valve to help

prevent dirt and fere^ materials from entering the gas control

valve.

• A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the ^ piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dty.

Standanl Modds are for installadon up to 3,300 feet above sea
level.

Altitude Models are for installation from 3,300 to 5,500

feet above sea level.
If a standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.

AWARNING

The appliance and its gas connection must be leak tested
before placing the appliance in operation.

14

This manual is related to the following products: