beautypg.com

A caution, Venting, Awarning – Kenmore POWER MISER 153.330551 User Manual

Page 13: Venting -14, Installation instructions (cont’d), Filling the water heater, Y. 1

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Installation Instructions (cont’d)

Filling the Water Heater

A CAUTION

Never use this water heater unless it is completely filled with

water. To prevent dam^ to the tank, the tank must be filled
with water. Water must flow from the hot water faucet

before turning “ON” gas to the water heater.

To fill the water heater with water:

• Close the water heater drain valve by turning the handle to

the right {clockwise). The drain valve is on the lower front of

the water heater.

• Open the cold water supply valve to the water heater.

NOTE: The cold water supply valve must be left open

when the water heater is in use.

• To insure complete filling of the tank, allow air to exit by

opening the nearest hot water faucet. Allow water to run

until a constant flow is obtained. This will let air out of the

water heater and the piping.

• Check all new water piping for leaks. Repair as needed.

Venting

AWARNING

VENT DAMPERS - Anf vent damper, whether it is operated
thermally or otherwise must be removed if its use inhibits prop­

er drafting of the water heater.

Thermally Operated Vent Dampers: Gas-fired water heaters

hawing thermal efficiency in excess of 80% may produce a rela­
tively low flue gas temperature. Such temperatures may not be

high enough to properly open thermally operated vent
dampers, lliis would cause spill^e of flue gases and may cause
carbon monoxide pdsoning.
Vent dampers must bear e^ence of certification as complying

with the latest edition of American National Standard ANSI
Z2I.68 (ANSI Z2I.66 & 67, respectively, cover electrically and

mechanically actuated vent dampers). Before installation of any

vent damper, consult your local Sears Service Center or the gas

utility for forteer information.

AWARNING

To insure proper venting of this gas-fired water heater, the

correct vent pipe diameter must be utilized. Any additions or
deletions of otter gas appliances on a common vent mth this
water heater may adversely affect the operation of the water
heater. Consult the local Sears Service Center or gas utility if
any such changes are planned.

For proper venting in certain installations, a larger diameter vent

pipe may be necessary. Due to great variances in installations,

unforeseeable by the manufacturer of the water heater, you must

consult your gas company to aid you in determining the proper

venting for your water heater from the vent tables in the latest

edition of the National Fuel Gas Code ANSI Z223.1, also

referred to as NFPA 54.
Check the venting system for signs of obstruction or deteriora­

tion and replace if needed.

The combustion and ventilation air flow must not be obstructed.

AWARNING

Obstructed or deteriorated vent systems may present a serious
health riti< or asphyxiation.

Place the draft hood legs in the receiving holes on the top of

the water heater. The legs will snap in the holes to give a tight

fit.

• Place the vent pipe over the draft hood. With the vent pipe in

position, drill a small hole through both the vent pipe and

draft hood. Secure them together with a sheet metal screw.

DRAFT HOOD

\

VENTv

SCRE'

L'll^

y. 1

*

I ^DDRAFT HOOD

DRAFT

VENT TO OUTDOORS OR

HOOD":i±«

AWARNING

The water heater with draft hood installed must be properly
vented to a chimney which terminates outdoors. Never opei^

ate the water heater unless it is vented to the outdoors and has
adequate air supply to avoid risks of improper operation, explo­
sion or asphyxiation.

AWARNING

The vent pipe from the water heater must be no less than the
diameter of the draft hood outlet on the water heater, and
must slope upward to the chimney at least % inch per linear
foot

13

This manual is related to the following products: