beautypg.com

Temperature-pressure relief valve, Caution, Warning – Kenmore POWER MISER 153.33616 User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Look at the top of the water heater. The cold water inlet is
marked “COLD”. Put two or three turns of teflon tape around

the threaded end of the threaded-to-sweat coupling and

around both ends of the 3/4” NPT threaded nipple. Using

flexible connectors, connect the cold water pipe to the cold
water inlet of the water heater.

NOTE: This water heater is super insulated to minimize
heat loss from the tank. Further reduction in heat loss
can be accomplished by insulating the hot water lines
from the water heater.

INSTALLATION COMPLETED USING

INSTALLATION KIT

FLEXIBLE

WATER

CONNECTORS

Temperature-Pressure Relief Valve

A

warning

Explosion Hazard

• Temperature-pressure relief valve

must comply with ANSI Z21.22

and ASME code.

Properly

sized

temperature-

pressure relief valve must be
installed in opening provided.

• Can result in overheating and

excessive tank pressure.

• Can cause serious injury or death.

This heater is provided with a properly certified combination

temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing
laboratory that maintains periodic inspection of production of
listed equipment of materials as meeting the requirements for
Relief Valves and Automatic Gas Shut-off Devices for Hot Water
Supply Systems, ANSI Z21.22 and the code requirements of

ASME.

If replaced, the valve must meet the requirements of local
codes, but not less than a combination temperature and
pressure relief valve certified as indicated in the above
paragraph.

The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water
heater (150 psi = 1,035kPa) and a discharge capacity not less

than the water heater input rate as shown on the model rating

plate.

For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve downward and provide tubing so that any
discharge will exit only within 6 inches (153 mm) above, or at
any distance below the structural floor, see Figure 16. Be certain

that no contact is made with any live electrical part. The

discharge opening must not be blocked or reduced in size
under any circumstances. Excessive length, over 30 feet
(9.14 m), or use of more than four elbows can cause restriction
and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should
circumstances demand. If the discharge pipe is not connected

to a drain or other suitable means, the water flow may cause

property damage.

CAUTION

Water Damage Hazard

■ Temperature-pressure relief valve discharge

pipe must terminate at adequate drain.

The Discharge Pipe:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.

• Shall be of material listed for hot water distribution.

• Shall be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge

pipe.

• Shall terminate at an adequate drain.

• Shall not have any valve between the relief valve and tank.

13