6.8 Avoid slugging
ATTENTION! Slugging can result in damage to the compressor and cause
refrigerant to leak.
To prevent slugging:
The complete refrigeration plant must be properly designed.
All components must be compatibly rated with each other with regard to output (particularly the
evaporator and expansion valves).
Suction gas superheating at the compressor input
should be > 10 K (check the setting of the
expansion valve).
The system must reach a state of equilibrium.
Particularly in critical systems (e.g. several evaporator points), measures such as the use of liquid
traps, solenoid valve in the liquid line, etc. are recommended.
There should be no movement of refrigerant in the compressor while the system is at a
standstill.
6| Commissioning
- HG5 (32 pages)
- HG7 (34 pages)
- HG4 (32 pages)
- HG6 (32 pages)
- HG8 (38 pages)
- HG34e (30 pages)
- HG22Р (26 pages)
- HG12Р (26 pages)
- BCM2000 (18 pages)
- HG22e (26 pages)
- HG34P (26 pages)
- HG88e (38 pages)
- HG44e (34 pages)
- HА4 (32 pages)
- HА34P (26 pages)
- HA12P (26 pages)
- HA5 (32 pages)
- HA6 (32 pages)
- HG22Р CO2 (28 pages)
- HG34P CO2 (28 pages)
- HG4 CO2 (30 pages)
- HG12Р CO2 (28 pages)
- HG12e CO2 (28 pages)
- HGX2 CO2 T (28 pages)
- HGX34 CO2 T (40 pages)
- HGX46 CO2 T (40 pages)
- HG5 R134a (32 pages)
- HG6 R134a (32 pages)
- HG7 R134a (32 pages)
- HG4 R134a (32 pages)
- HGZ7 (42 pages)
- F (44 pages)
- F18 (28 pages)
- FK40 (26 pages)
- FK30 (26 pages)
- FK50 (26 pages)
- FK20 (26 pages)
- HG22P A (28 pages)
- HG34e A (28 pages)
- HG22e A (28 pages)
- HGX34P 2 pole (32 pages)