4 | compressor assembly – GEA Bock HAX2 CO2 T User Manual
Page 11
![background image](/manuals/657490/11/background.png)
D
GB
F
E
11
96031-02.2015-DGbF
4| Compressor assembly
•
The compressor has a shut-off valve with multi-sided cutting ring for the safe installation of the
suction and discharge line.
Cutting ring function before tightening the union nut
.
.
.
.
.
.
4.7 Pipe connections
Fig. 17
Valve spindle seal
release
tighten
4.6 Operating the shut-off valves
Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn
counter-clockwise.
After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
Fig. 15
Fig. 16
4.8 Laying suction and discharge line
INFO!
Proper layout of the suction and pressure lines directly after the
compressor is integral to the smooth running and vibration
behaviour of the system.
Procedure:
Push Union Nut (5) and Cut Ring (3) onto Pipe (2).
Hand tighten Union Nut (5) until locked.
Insert Pipe (2) firmly into rebate located in Socket (6) ensuring the pipe fits snugly. Tighten
Union Nut (5) 1 ½ turns using a spanner/wrench, while gripping connecting Socket (6) with
another spanner/wrench. This should cause the Cutting Edge (1) of Cut Ring (3) to Cut into
Pipe (2) resulting in a visible collar.