7 | maintenance – GEA Bock HG34P CO2 User Manual
Page 22

22
 D
 GB
 F
 E
09918-02.2015-DGbFEI
7| Maintenance
7.5 Extract from the lubricants table
HGX34P / ...
215-4 CO
2
255-4 CO
2
Designation
Item No.
Item No.
Set of gaskets
80367
Valve plate kit
80305
Set piston/connecting rod
80366
80468
Set connecting rod
80368
Only use genuine GEA Bock spare parts!
7.3 Spare parts recommendation
For operation with CO
2
the oil GEA Bock C 85 E is necessary!
7.1 Preparation
7.2	 Work	to	be	carried	out
In order to guarantee optimum operational reliability and service life of the compressor, 
we recommend
carrying out servicing and inspection work at regular intervals:
Oil change:
-
not mandatory for factory-produced series systems.
-
	for	field	installations	or	when	operating	near	the	application	limit:	for	the	first	time	after	100	
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours. 
Dispose of used oil according to the regulations; observe national regulations.
Annual	 checks: Oil level, leak tightness, running noises, pressures, temperatures, function of 
 auxiliary devices such as oil sump heater, pressure switch.
WARNING!	 Before	starting	any	work	on	the	compressor:
 
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch-on lock.
Available accessories can be found on the Internet at www.gea.com