5 | electrical connection – GEA Bock HG34P CO2 User Manual
Page 17

 D
 GB
 F
 E
17
09918-02.2015-DGbFEI
ATTENTION! The oil sump heater must generally be connected and operated.
Connexion: The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary 
contact) of the compressor contactor to a seperate electric circuit.
Electrical data: 110 - 240 V - 1 - 50/60 Hz, 50 - 120 W, PTC-heater adjusting.
5| Electrical connection
The compressor and the trigger unit MP10 are operational when the H3 LED (green) lights.
5.6 Function test of the trigger unit MP 10
Pos
Procedure
LED H1 LED H2 LED H3
red
red
green
1 • Interrupt power supply (L1 or S1)
OFF
OFF
OFF
•
Release the motor temperature sensor connection (1 or 2)
•
Release the hot gas temperature sensor (if installed) (3 or 4)
2 • Restore the power supply (L1 or S1)
ON
•
Function check of motor temperature sensor: operational
ON
•
Function check of hot gas temperature sensor: operational
ON
3 •
Interrupt power supply again (L1 or S1)
OFF
OFF
OFF
•
Reconnect terminals 1 or 2 and/or 3 or 4
4 •
Restore the power supply (L1 or S1):
OFF
OFF
ON
•
MP 10 is operational again
Before start-up, troubleshooting or making changes to the control power circuit, check the functionality 
of the trigger unit:
5.7 Oil sump heater (accessories)
In	order	to	avoid	damage	to	the	compressor,	the	compressor	must	be	equipped	with	an	oil	sump	
heater.