7.1 Preparation

7.2 Work to be carried out

7| Maintenance

In order to guarantee optimum operational reliability and service life of the compressor,

we recommend

carrying out servicing and inspection work at regular intervals:

Oil change:

-

not mandatory for factory-produced series systems.

-

for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.

Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.

WARNING! Before starting any work on the compressor:

Switch off the compressor and secure it to prevent a restart.

Relieve compressor of system pressure.

Prevent air from infiltrating the system!

After maintenance has been performed:

Connect safety switch.

Evacuate compressor.

Release switch-on lock.

6.8 Connection of oil level regulator
The connection "O" is provided for installing an oil level regulator. A corresponding adapter must be
obtained from the trade.

6| Commissioning

Only use genuine GEA Bock spare parts!

7.3 Spare parts recommendation

HG12P / ...

60-4 S

75-4 (S)

90-4 (S)

110-4 (S)

Designation

Ref. No.

Ref. No.

Ref. No.

Ref. No.

Set of gaskets

80339

Valve plate kit

80352

80353

Oil pump kit

08324