Electrical work
Noise considerations
• Always use at the rated voltage.
• Some installation locations may require installation of
a shortcircuit breaker.
• A16 Ampere (CW-C200SR, CW-A200SR), 20 Ampere
(CW-C240SR, CW-A240SR) time delay fuse or circuit
breaker is required.
• Nominal cross sectional area of power supply wire
must be 3 core x 1.5 mm^ {CW-C200SR, CW-A200SR)
and 3 core x 2.5 mm^ (CW-C240SR, CW-A240SR) or
above.
• The power supply must be from an independent circuit.
® All electrical installation must be made in
accordance with local wiring and safety regulations
wherever applicable.
• Please consult your dealer concerning installation
requirements.
Transferring
When repositioning the air conditioner due to
renovations, or when transferring to a different
location, the removal and réinstallation of the unit
requires an additional service charge. Please consult
your dealer before moving.
Rernqval of the grilie
1) REMOVE AIR FILTER
2) REMOVE FRONT GRILLE
• Loosen the screws at the right, left and centre of the
grille.
• Press the side of the cabinet firmly and at the same
time pull the corner of the grille forward to
unhook the tabs.
• Slide the grille upward to free the two tabs at the
top of the grille from slots at the top of the cabinet.
CABINET
• Select an installation location that can support the
weight of the air conditioner and one that will not cause
increased operating noise and vibration.
• Ensure that airflow and noise from the rear side
of the unit (outdoors) when installed do not cause
inconvenience to neighbouring residents.
• Obstacles placed in front of the air outlet on the
rear side of the unit (outdoors), or covers placed
over it, cause excessive noise and a deterioration in
performance.
Drain water
To get the maximum cooling efficiency this air
conditioner is designed to splash the condensate
on the condenser coil.
This method is called “Slinger-Up System”. (For cooling
model only)
If the splashing sound annoys you, you can provide
an outside drain by using the following procedure
which
may,
however
cause
a
small
loss
of
performance.
1. Slide out the chassis from the cabinet.
2. Remove the rubber plug from the body base plate.
(For cooling model only)
3. Install the drain pan prepared in the accessory kit to
the corner of the cabinet with 2 screws.
4. Connect the drain hose to the outlet on the drain pan
bottom.
5. Slide the chassis into its original place in the cabinet.
Note: Drain hose or tubing can be purchased locally to
satisfy your particular needs.
-