DV360/580 Series Direct Vent Gas Fireplace

20010667

Troubleshooting the Gas Control System

SIT 822 Valve with Synetek Electronic Control

Operating Diagram

Normal Operation

ON/OFF Switch Closed?

Safe Start Check On?

0 Sec Purge

Pilot Flame Sense OK?

ON/OFF Switch Opened?

Pilot and Main Valve OFF?

0 sec Post Purge?

Ignition Trial: 30 sec Spark ON

Pilot Valve ON. Has Flame

been Detected within 30 sec?

Spark Off. Main Valve ON.

Pilot Flame Continuously

Monitored

Heating Cycle Complete LED:

OFF

NO

YES

NO

NO

YES

Abnormal Operation

5 sec Inter-Trial Delay

LED: Steady Flash?

Lockout: Flame detected out of sequence

Reset by interrupting ON/OFF switch or

power for 10 sec

LED: 5 Flashes?

Reverse power cord polarity

LED: 2 Flashes?

Reset by interrupting ON/OFF

switch for power for 10 sec

Pilot, Valve OFF, Spark OFF

Have three ignition trials been completed?

LED: 3 Flashes?

Lockout: Flame Loss

Reset by interrupting ON/OFF switch or

power for 10 sec

Main Valve OFF, Spark ON

Has flame been detected within 30 sec?

Have three pilot flame losses been

detected?

NO

YES

NO

YES

YES

YES

YES