Building Technologies

CC1N7865en

HVAC Products

01.09.2005

Function of the controller when used for burner control (cont´d)


To acquire the actual value, a number of sensors can be connected to the RWF40...

Measurement

range

Pt100 / IEC 751

-200...+850 °C (-328...+1562 °F)

Pt1000 / IEC 751

-200...+850 °C (-328...+1562 °F)

Ni100 / DIN 43760

-60...+230 °C (-76...+482 °F)

Ni1000 / DIN 43760

-60...+230 °C (-76...+482 °F)

2-or 3-wire resistance

sensors

LG-Ni1000

-50...+160 °C (-58...+320 °F)

Thermocouples

NiCr-Ni / type «K»

-200...+1372 °C (-328...+2502 °F)

Cu-Cu-Ni / type «T»

-200...+400 °C (-328...+752 °F)

NiCroSil-NiSil / type «N»

-100...+1300 °C (-148...+2372 °F)

FeCuNi / type «J»

-200...+1000 °C (-328...+1832 °F)

Pt-RhPt / type «S»

0...1768 °C (-32...3214 °F) ¹)

Pt-RhPt / type «R»

0...1768 °C (-32...3214 °F) ¹)

Pt-RhPt / type «B»

0...1820 °C (32...3308 °F) ¹)

0...20 mA

scalable -1999...+9999

4...20 mA

scalable -1999...+9999

DC 0...10 V

scalable -1999...+9999

Linearized standard

signals

DC 0...1 V

scalable -1999...+9999

¹) Only RWF40.0X2B97


The power provided for the measuring transducers is DC 24 V / 30 mA.

Feeding a signal to analog input 2, the controller´s setpoint can be influenced. The
influence can be scaled.

The following signals can be used:

-

Input signals DC 0...1 V, DC 0...10 V, 0...20 mA, 4...20 mA

-

1 k

Ω potentiometer in a 2-wire circuit

Analog input 1 (actual
value sensor)

Analog input 2 (external
setpoint shift or external
setpoint)