Function of the controller when used for burner control

In low-fire operation, the RWF40... operates like a control thermostat or pressurestat.
This means that it operates as a 2-position controller maintaining the required setpoint
by switching the burner on and off. The switching differential for 2-position operation
can be adjusted within a wide range. If the demand for heat increases, the controller
switches to high-fire operation only when an adjustable limit is exceeded. This function
is aimed at optimizing the burner´s switching ratio.

In that case, the RWF40... operates as a 2-position controller with adjustable switching
thresholds. Using the relays of the 3-position output, the RWF40... drives the actuator
to the 1

st

and 2

nd

output stage. In this operating mode, the optional analog output

switches between the minimum signal for the 1

st

stage and the maximum output signal

for the 2

nd

stage.


In that case, the RWF40... operates as a PID / PI controller with a 3-position output
without position feedback signals or, optionally, with a modulating output. By making
use of its self-setting facility, the RWF40... is able to determine the PID / PI control
parameters, or the parameters can be set manually.

Using a potential-free contact, the RWF40... can be switched from the modulating
mode to 2-stage operation.

In the case «setpoint shifting» is configured, the current setpoint is shifted by an adjust-
able amount. Configuration of «setpoint changeover» provides changeover between 2
setpoints adjusted on the RWF40... If analog input 2 is configured for an «external set-
point», changeover is provided between the setpoint adjusted on the RWF40... and an
external setpoint.

Potential-free contact «K6» can be assigned a number of functions.
Example: Limit value supervision

4 buttons on the unit front are used to operate and program the RWF40... During op-
eration and programming, the 7-segment displays show the parameter values and pa-
rameter names.

The controller´s standard configuration ex works is such that when connecting a
QAC22… outside sensor, automatic changeover to weather-dependent setpoint shifting
takes place.

The signal delivered by the QAC2... outside sensor must not be fed parallel to sev-
eral RWF40...!

Low-fire operation

High-fire operation,
2-stage control

High-fire operation,
modulating control

Binary input 1 (change-
over of operating mode)

Binary input 2 (setpoint
shifting or setpoint
changeover)

Limit comparator

Operation

Weather-dependent
setpoint shifting