Kidde P12040 User Manual

Page 6

background image

• When mixing models which have battery backup (i12040, i12040A,

i12060, i12060A, i12080, i12080A, i12090A, i4618, i1418A, 1275,
1276, 1285, 1296, PE120, P12040, PI2000, PI2010, KN-COSM-
IB, RF-SM-ACDC, KN-COPE-I, KN-SMFM-I, HD135F, KN-COB-IC,
KN-COP-IC) with models without battery backup, (i1235, i12020,
i12020A, KN-COSM-I SM120X, CO120X, SL177I) be advised that
the models without battery backup will not respond during an AC
power failure.

• The maximum wire run distance between the first and last unit in

an interconnected system is 1000 feet.

• Figure 4 illustrates interconnection wiring. Improper connection

will result in damage to the alarm, failure to operate, or a shock
hazard.

• Make certain alarms are wired to a continuous (non-switched)

power line. NOTE: Use standard UL listed household wire (as
required by local codes) available at all electrical supply stores and
most hardware stores.

FIGURE 4 INTERCONNECT WIRING DIAGRAM

WIRES ON ALARM HARNESS CONNECTED TO

Black

Hot Side of AC Line

White

Neutral Side of AC Line

Red

Interconnect Lines (Red Wires) of

Other Units in the Multiple

Station Set up

BATTERY INSTALLATION

See Maintenance (section 6) for battery installation

CAUTION! IF BATTERY REMINDER FINGER IS NOT HELD DOWN
IN THE BATTERY COMPARTMENT BY THE BATTERY, THE
BATTERY DOOR WILL NOT CLOSE, THE AC QUICK CONNECTOR
WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT
ATTACH TO THE TRIM RING (SEE SECTION 6, FIGURE 9).

FUSE OR CIRCUIT BREAKER

RED

BLACK

WHITE

BLACK

WHITE

RED

CONNECTOR

CONNECTOR

Kidde

Relay Module

SM120X

First
Alarm

Additional
Alarm

Optional

Accessory

Additional
Alarm