Ceiling mounting is preferred in ordinary residential construction.

• For mobile home installation, select locations carefully to avoid

thermal barriers that may form at the ceiling. For more details,
see MOBILE HOME INSTALLATION below.

• When mounting an alarm on the ceiling, locate it at a minimum

of 4” (10cm) from the side wall (see figure 1).

• When mounting the alarm on the wall, use an inside wall with

the top edge of the alarm at a minimum of 4” (10cm) and a
maximum of 12” (30.5cm) below the ceiling (see figure 1).

• Put smoke alarms at both ends of a bedroom hallway or large

room if the hallway or room is more than 30 ft (9.1m) long.

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at

or within 3 ft (0.9m) of the highest point (measured horizontal-
ly). NFPA 72 states: “Smoke alarms in rooms with ceiling slopes
greater than 1 ft in 8 ft (.3m in 2.4m) horizontally shall be locat-
ed on the high side of the room.” NFPA 72 states: “A row of
alarms shall be spaced and located within 3 ft (0.9m) of the
peak of the ceiling measured horizontally” (see figure 3).