Ryobi RYI1000 User Manual
Page 6
2 — English
KEEP AT LEAST
20 FT. AWAY
CO Detector
in Living Areas
Only use OUTSIDE and
FAR AWAY from windows,
doors, and vents.
Exhaust (CO)
Direct exhaust AWAY
from all windows, doors,
and vents.
LOCATE GENERATOR AT LEAST 20 FT.* AWAY TO REDUCE THE
RISK OF CARBON MONOXIDE GETTING INSIDE THE HOME
*
Minimum distance as recommended by U.S. Department of Health and Human
Services Centers for Disease Control and Prevention (www.cdc.gov/co). Your specific
home and/or wind conditions may require additional distance.
To register your Ryobi product,
please visit: www.ryobitools.com/
WARNING:
GROUNDING THE GENERATOR
If this generator will be used
only with cord and plug-connected
equipment, National Electric Code does not require that the unit be
grounded. However, other methods of using the generator may require
grounding to reduce the risk of shock or electrocution. Consult a quali-
fied electrician, electrical inspector, or local agency having jurisdiction
for local codes or ordinances to find out if grounding is needed in your
situation before using the generator.
When grounding is required, the nut and ground terminal on the frame
are used to connect the generator to a suitable ground source. The
ground path should be made with #8 size wire. Connect the terminal of
the ground wire between the lock washer and the nut, and tighten the
nut fully. Connect the other end of the wire securely to a suitable ground
source that is in contact with the soil for a minimum distance of 8 ft.
The National Electric Code contains several practical ways in which to
establish a good ground source. If a steel or iron rod is used, it should
be at least 5/8 in. diameter, and if a nonferrous rod is used, it should
be at least 1/2 in. diameter and be listed as material for grounding. If
a rock bottom is encountered before reaching a depth of 8 ft., drive
the ground rod in at an angle of up to 45
°. If the rock bottom is again encountered, the rod can be buried in a trench
that is at least 30 in. deep. In all cases, the upper end of the grounding rod should either be flush with (or below) the
ground or must be otherwise protected from physical damage.
All electrical tools and appliances operated from this generator must be properly grounded by use of a third wire or
be “Double Insulated.”
It is recommended to:
1. Use electrical devices with 3-prong grounded plugs.
2. Use an extension cord intended for outdoor use with a 3-pole receptacle and a 3-prong plug at opposite ends to
ensure continuity of the ground protection from the generator to the appliance.
Check and adhere to all applicable federal, state, and local regulations relating to grounding specifications. Consult a
qualified electrician or service personnel if the grounding instructions are not completely understood or if in doubt as
to whether the generator is properly grounded.