Ryobi RYI2200H User Manual
Page 6
2 — English
KEEP AT LEAST
20 FT. AWAY
CO Detector
in Living Areas
Only use OUTSIDE and
FAR AWAY from windows,
doors, and vents.
Exhaust (CO)
Direct exhaust AWAY
from all windows, doors,
and vents.
LOCATE GENERATOR AT LEAST 20 FT.* AWAY TO REDUCE THE
RISK OF CARBON MONOXIDE GETTING INSIDE THE HOME
*
Minimum distance as recommended by U.S. Department of Health and Human
Services Centers for Disease Control and Prevention (www.cdc.gov/co). Your specific
home and/or wind conditions may require additional distance.
To register your Ryobi product,
please visit: www.ryobitools.com
WARNING:
GROUNDING THE GENERATOR
If this generator will be used
only with cord and plug-connected
equipment, National Electric Code does not require that the unit be
grounded. However, other methods of using the generator may re-
quire grounding to reduce the risk of shock or electrocution. Consult
a qualified electrician, electrical inspector, or local agency having
jurisdiction for local codes or ordinances to find out if grounding is
needed in your situation before using the generator.
When grounding is required, the nut and ground terminal on the
frame are used to connect the generator to a suitable ground
source. The ground path should be made with #8 size wire. Con-
nect the terminal of the ground wire between the lock washer and
the nut, and tighten the nut fully. Connect the other end of the wire
securely to a suitable ground source that is in contact with the soil
for a minimum distance of 8 ft.
The National Electric Code contains several practical ways in which to establish a good ground source. If a steel or
iron rod is used, it should be at least 5/8 in. diameter, and if a nonferrous rod is used, it should be at least 1/2 in. di-
ameter and be listed as material for grounding. If a rock bottom is encountered before reaching a depth of 8 ft., drive
the ground rod in at an angle of up to 45
°. If the rock bottom is again encountered, the rod can be buried in a trench
that is at least 30 in. deep. In all cases, the upper end of the grounding rod should either be flush with (or below) the
ground or must be otherwise protected from physical damage.
All electrical tools and appliances operated from this generator must be properly grounded by use of a third wire or
be “Double Insulated.”
It is recommended to:
1. Use electrical devices with 3-prong grounded plugs.
2. Use an extension cord intended for outdoor use with a 3-pole receptacle and a 3-prong plug at opposite ends to
ensure continuity of the ground protection from the generator to the appliance.
Check and adhere to all applicable federal, state, and local regulations relating to grounding specifications. Consult a
qualified electrician or service personnel if the grounding instructions are not completely understood or if in doubt as
to whether the generator is properly grounded.