Table 4. Installation Clearances.

Ref Description

Canadian

Installations

US

Installations

A

Clearance above grade, veranda,

porch, deck, or balcony

12 inches

(30 cm)

12 inches

(30 cm)

B

Clearance to window or door that

may be opened

36 inches

(91 cm)

12 inches

(30 cm)

C

Clearance to permanently closed

window

* *

D

Vertical clearance to ventilated

soffit, located above the terminal

within a horizontal distance of 2

feet (61 cm) from the center line of

the terminal

* *

E

Clearance to unventilated soffit

*

*

F

Clearance to outside corner

*

*

G

Clearance to inside corner

*

*

H

Clearance to each side of center

line extended above

meter/regulator assembly

3 feet (91 cm)

within a height

15 feet (4.5 m)

above the

meter/regulator

assembly

*

I

Clearance to service regulator vent

outlet

36 inches

(91 cm)

*

J

Clearance to non-mechanical air

supply inlet to building or the

combustion air inlet to any other

appliance

36 inches

(91 cm)

12 inches

(30 cm)

K

Clearance to a mechanical air

supply inlet

6 feet (1.83 m)

3 feet (91

cm) above if

within 10 feet

(3 m)

horizontally

L

Clearance above paved sidewalk

or paved driveway located on

public property

7 feet

(2.13 m) ♦

*

M

Clearance under veranda, porch,

deck, or balcony

12 inches

(30 cm) ▲

*


♦ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two
single family dwelling and serves both dwellings.

▲ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the
floor.

* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance
with local installation codes and the requirements of the gas supplier.