Control Timings
Ignition State
Timing
Pre-purge
15 Seconds
Trial for Ignition
90 Seconds
Flame Stabilization Period
3 Seconds
Inter-purge
15 Seconds
Flame Failure Response Time
1.5 Seconds (2 second. Maximum; 1 second minimum.)
Post-purge
15 Seconds
PS Fault Delay (failed open/close)
Retry after 2 Minutes
Soft Lockout
Retry after 5 Minutes
TCO Limit Lockout
Indefinite (cycle power to restart)
Simulated Resistive Load Lockout
Indefinite (cycle power to restart)
Hardware Error Lockout
Indefinite (self clears if fault clears for at least 15 seconds)
Verify Resistive Delay
Retry after 2 Minutes (repeats 5 times)