beautypg.com

Bradford White M-2-TW-75T6SX User Manual

Page 16

background image

16

Venting (Part I) continued-

TABLE 3

3” (7.6 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL FOR

LOW GROUND CLEARANCE INSTALLATIONS

Max Straight
Length
ft (m)

Terminating #

of

Elbows

48,65

gal.

75 gal.

Min

straight

Length

ft (m)

(2) 90

° Elbows with (1) 90° Elbow

1

45 (13.7) 35 (10.7)

5 (1.5)

(2) 90

° Elbows with (1) 90° Elbow

2

40 (12.2) 30 (9.1)

5 (1.5)

(2) 90

° Elbows with (1) 90° Elbow

3

35 (10.7) 25 (7.6)

5 (1.5)

(2) 90

° Elbows with (1) 90° Elbow

4

30 (9.1) 20 (6.1)

5 (1.5)

TABLE 4

4” (10.2 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL FOR

LOW GROUND CLEARANCE INSTALLATIONS

Max straight
Length
ft (m)

Terminating (Reduce 4” to 3”)

(Reduce 10.1 cm to 7.6 cm)

# of

Elbows

48,65

gal.

75 gal.

Min

straight

Length

ft (m)

(2) 90

° Elbows with (1) 90° Elbow

1

75 (22.9) 65 (19.8)

10 (3.1)

(2) 90

° Elbows with (1) 90° Elbow

2

70 (21.4) 60 (18.3)

10 (3.1)

(2) 90

° Elbows with (1) 90° Elbow

3

65 (19.8) 55 (16.8)

10 (3.1)

(2) 90

° Elbows with (1) 90° Elbow

4

60 (18.3) 50 (15.2)

10 (3.1)

(2) 90

° Elbows with (1) 90° Elbow

5

55 (16.8) 45 (13.7)

10 (3.1)

HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER 2,500
FEET (762 m)
ABOVE SEA LEVEL

The capacity of the induced draft blower declines with increasing altitude due to
a reduction in the air density. In order to assure safe and reliable performance
of the water heater, contact the supplier for high altitude kit.

This manual is related to the following products: