I

n case there is excessive frost, the parameters FnC = C-y, idF = 4 and MdF =

20 can be used to avoid frost.


9. How to adjust the humidity

The parameter Fon is used to adjust the humidity in the wine cellar. Higher Fon
results in higher relative humidity.

Use a separate hygrometer to monitor the

humidity.

10. How to set alarm call

1) S

peech notice will be sent to your phones when the cellar temperature is ALU

higher or ALL lower than the set-point Set.

2) In order to test the call function, set parameters Ald = 0 and dAO = 0. After
testing, set Ald = 60 and dAO = 23.

11. How to set low cellar temperature heater

The heater turns on at SAA minus Shy; the heater turns off at SAA.
NOTES:

• Use a forced air heater to warm up the wine cellar.

• If there is a thermostat on the heater, bypass it or set the thermostat at the

highest level.

If the heater runs more than 10 A current, use a 120VAC coil contactor.