Standard Protection Mechanisms
The cooling unit is programmed to shut down certain components to protect
those components, as well as the wine inside the cellar, under the following
circumstances:
Scenario
What it means
What happens
P1 Alarm
Probe 1, which senses the
temperature inside the cellar
and controls the on/off cycles
of the cooling unit, has failed
The cooling unit enters a
timed auto-cycle mode until
Probe 1 is repaired or
replaced. In this mode, the
cooling unit will turn on for
12 minutes and off for 8
minutes.
Optional Protection Mechanisms
CellarPro cooling systems can be programmed to turn off the compressor and
condenser fan in the event of an HA2 alarm, as described below. If you’d like to
turn on this protection mechanism, please call us toll-free at 877.726.8496.
Scenario
What it means
What happens
P3 > 140° F
for More than
2 hours
The condenser probe is
measuring temperatures that
are too hot
The compressor and
condenser fan will turn off
until the condenser
temperature falls below
140°F