Universal Remote Control (URS) Thermo Control User Manual
Page 11
Thermo Control for THZ-100 Thermostat
9
Button Lockout
allows you to add a 4 digit lockout code when enabled. locking the keypad is a good
idea to avoid unwanted people from controlling the thermostat. Check the Use
Pass-Code Lockout to enable the lockout feature.
Set Point Limiter
This feature allows you to set a heat limit and a cool limit by manually entering a limit
point for both. This prevents users from making temperature adjustments outside of the limit range.
1. Click the Limit Heat To Set Point drop-down box to select a limit point.
2. Click the Limit Cool To Set Point drop-down box to select a limit point.
Multistage HVAC Setting
when a two stage heating or two stage cooling system is selected, these options are available for setting.
This value determines when the thermostat will call for 2nd stage heating/cooling.
2nd Stage Heating Offset: This feature is enabled if a 2 Heating system is in use.
2nd Stage Cooling Offset: This feature is enabled if a 2 Cooling system is in use.
Auxiliary Heat Offset: enabled when HvaC system type “Heat pump with auxiliary heat” is chosen.This
sets the value for Auxiliary Heat Offset.
Auto Mode Temperature Override/Hold Behavior
This option determines how the thermostat behaves when the preset temperature is adjusted while in Auto
Mode. refer to User manual for auto Mode description.
Maintain Exact Temperature Within
This feature allows the thermostat to limit compressor cycles and reduce energy consumption by
maintaining the temperature within the variance chosen for this setting.
when this parameter is set to 2°, the thermostat will not engage the compressor (turn on) until the
temperature is at least 2° from the desired set-point.
Example
Maintain exact Temperature within: 4° set-point: 74°
while in Heat Mode the thermostat will not engage the heat until temperature reaches 70°.
while in Cool Mode the thermostat will not engage the a/C until temperature reaches 78°.
System Cycle Limit
Maximum Cycles per Hour
This option sets the value for maximum number of heating or cooling cycles that may be called for per hour.
● Click the Heating drop-down box to set the Maximum Cycles per hour.
● Click the Cooling drop-down box to set the Maximum Cycles per hour.
Compressor Protection/Compressor Delay (set in minutes)
This option sets the minimum number of minutes between successive heating or cooling activation cycles,
including activation of a heating cycle following a cooling cycle or a cooling cycle following a heating cycle.
1. Click the Compressor Delay drop-down box to set the delay time in minutes.
Thermo Control for THZ-100 Thermostat