Smart Power Systems ER Series User Manual
Page 35
Smart Power
®
Systems
A. C. MODULAR GENERATOR SYSTEM
Page 34 of 52
Lubricate the oil filter gasket with Dexron III before installation to permit
proper sealing of the filter.
WARNING:
Do not by-pass the filter or alter filtration plumbing in any way. Doing so will void
the system’s warranty.
3.
The system controller automatically records the time from the previous filter change.
The hours since the previous filter change can be accessed using the Command &
Control Center by pressing the Mode switch until the following screen appears
(reference Figure 24):
Time Since last Oil Filter
Change in Hours.
Press Mode until FLt
and Xr are displayed
Example of oil filter run time display
Figure 24
4.
The Command & Control Center will flash a fault when 250 hours have passed
since the previous filter change. After replacing the filter, this fault can be removed
from the Command & Control Center, and the filter run time can be reset by
performing the following steps: