Smart Power Systems ER Series User Manual
Page 30

Smart Power
®
Systems
A. C. MODULAR GENERATOR SYSTEM
Page 29 of 52
The system controller is 
configured to operate a generator 
whose maximum output is this 
number (in kW). 
The Er indicates the system 
controller is configured to 
operate an ER-series 
Generator 
Example of configuration display
Figure 18
d. If there are no active faults, pressing the Mode switch once more will return the
Command & Control Center to its normal mode. If there are active faults, they 
will be displayed in succession, one each time you press the Mode switch. 
See Diagnostics in the trouble shooting section for more information on faults.
 
8. 
If the system measures a hydraulic oil temperature that exceeds 175
F (79C), the
system will begin displaying an alarm. If the system measures a hydraulic oil 
temperature that exceeds 180
F (82C), the generator will automatically shut down
in 30 minutes unless the shutdown is overridden. If the temperature of the hydraulic 
oil is measured at or above 220
F, the system will immediately shut down unless
the high temperature oil warning is overridden. To override the shutdown, perform 
the following steps: 
Note: The system must measure a hydraulic oil temperature that exceeds 180
F for
this procedure to work.
Step a: Press Mode to 
cause rvn and the y and 
n labels to appear.
Step b: Press On/Off to 
answer “yes” and make 
the next screen appear.
Example of Command & Control Center in hot oil fault override
Figure 19
 
 