Kontron CP3-SVE-P200DC User Manual
Page 9
CPCI Power Supply
PD06: CP3-SVE-P200DC
RID 24139 PD06, Rev. 01
© 2002 PEP Modular Computers GmbH
Page 9
PROTECTION AND CONTROL
PARAMETER
CONDITIONS/DESCRIPTION
MIN
NOM
MAX
UNITS
Overvoltage
Protection
Latch style overvoltage protection.
120
130
%Vnom
Overload Protection
Fully protected against output overload and short cir-
cuit. Automatic recovery upon removal of overload
condition.
Available
Overtemperature
Protection
System shutdown due to excessive internal tempera-
ture, automatic reset.
Available
Power Fail (FAL#)
TTL compatible signal, open collector active low sig-
nal. Indicates any output below 90% and/or a low
input <36VDC.
Available
Current Share
Accuracy of shared current with up to 6 parallel units
of the same type of power supply. Single wire current
share on V1, V2, and V3.
10
%
Remote Sense
Available on V1, V2, and V3. Total voltage compensa-
tion for cable losses with respect to the main output.
150
mV
Inhibit (INH#)
TTL-compatible signal inhibited with GND or TTL "0".
Available
Enable (EN#)
Contact closure to external ground to start unit. On
shortest pin (last make, first break).
Available
Overtemperature
Warning (DEG#)
Provides warning when power supply temperature
exceeds rating. TTL-compatible open.
Available
Front Panel LED
Status Indicators
Input OK (Green), Output Failure (Red). In redundant
setups, Output Failure may also indicate that there is
no main power input to the power supply.
Available
SAFTEY, REGULATORY, AND EMI
PARAMETER
CONDITIONS/DESCRIPTION
MIN
NOM
MAX
UNITS
Agency Approvals
UL1950, cUL1950, EN60950 (TÜV).
Approved
Dielectric Withstand
Voltage
Input to Output per EN60950.
4243
VDC
Electromagnetic
Interference
EN55022 / CISPR 22
Conducted:
Radiated:
A
A
Class
ESD Susceptibility
Per EN61000-4-2, level 4.
8
kV
Radiated
Susceptibility
Per EN61000-4-3, level 3.
10
V/m
EFT/Burst
Per EN61000-4-4, level 3.
± 2
kV
Input Surge
Per EN61000-4-5, level 3.
Line to Line
Line to Ground
1
2
kV