WV410 WINDOW - INSTALLATION INSTRUCTIONS

Section IX – Casement Lift Block Installation


Due to the weight of the vent, lift blocks are used to elevate the vent upon closing. Elevating the

vent aligns the gaskets and cam locks to the proper location. All WV410 casement vents receive

one (1) or two (2) pairs of lift blocks, depending on the vent size. Casement vents over 30” wide
will receive two (2) pairs and vents under 30” will receive one (1) pair. The blocks are designed

to be located directly over each other. The vent portion of the lift block pair will be preinstalled
by EFCO.


Step 1

Locate the center line of the lift block HB64 as required per the vent size. See Figure 24. Check

the lift block location mounted on the vent for correct center line.

Step 2

Drill (2) .136” diameter (No. 29 drill) holes per block through the storefront framing shown in

Figure 24, and install with (2) SFZ5 fasteners per lift block.

Step 3

The operable vent may now be installed. Reinstall the operable vent to the WV410 frame. Be
sure to mount the vent and hinges in the same locations preinstalled by EFCO. See section IX on

Page 20.