* * I M P O R T A N T * *
I N S T A L L E R S M U S T F I L L O U T T H I S S H E E T A N D
F A X T O
7 0 7 . 7 9 4 . 8 0 0 5 O R S C A N / E M A I L T O I N F O @ C E L L A R P R O . C O M
T O A C T I V A T E T H E W A R R A N T Y .
Installing CellarPro Split Systems requires an experienced professional and adherence to industry practices which
are described in the manual. To activate the warranty, the cooling unit must be installed properly. In order for us to
assess and approve the installation, the installing technician must complete the page below. The page can be faxed
to 707.794.8005 or emailed to [email protected]. We will contact you once we receive and review this sheet.
Technician Name
Tech Phone
System Information
Piping Information
Customer Name
R-134a system charge lb.
Condensing Unit Model #
Line-set length – ft.
Condensing Unit Serial #
Liquid line diameter – OD
Evaporator Model #
Suction line diameter - OD
Evaporator Serial #
Power to Condensing Unit (Check One)
___ From Evaporator ___ From External Source
Operational Data
Take the following measurements during a normal refrigeration cycle, once the cellar has pulled down to
the set-point temperature. Make sure the compressor is running when recording the data.
Evaporator
Comment
Air temperature at Evaporator coil inlet/outlet
°F/°F
8-10°F TD
Evaporator fan speed (High / Med / Low)
Evaporator power supply voltage & amps
V & A
103-127 V – check
nameplate amps
Condensing Unit
Air temperature at Condenser coil inlet & outlet
°F/°F
20-30°F TD
Condenser fan status (ON / OFF)
Suction pressure at suction service valve
PSIG
25-35 PSIG
Suction temperature at suction service valve
°F
20°F Superheat Min.
Liquid pressure at liquid service valve
PSIG
105-180 PSIG
Liquid temperature at liquid service valve
°F
10-20°F Subcooling
Condensing Unit power supply voltage & amps
V & A
103-127 V – check
nameplate amps