CellarPro 4000SWC SPLIT SYSTEM WATER COOLED, 7649 User Manual
Page 28
![background image](/manuals/635122/28/background.png)
28
V10.14
System R-134a Charge Guidelines
Actual
Line
Length
(ft)
4000Swc, Shwc
8000Swc
5
1.35
3.31
10
1.55
3.52
15
1.75
3.72
20
1.95
3.92
25
2.15
4.13
30
2.35
4.33
35
2.55
4.53
40
2.75
4.74
45
2.95
5.04
50
3.15
5.25
55
3.35
5.46
60
3.55
5.68
65
3.75
5.89
70
3.95
6.11
75
4.15
6.32
80
4.35
6.53
85
4.55
6.75
90
4.75
6.96
Note:
1) Actual charge may vary - follow charging instructions
detailed under Item 6 in the section titled Evacuation,
Leak Detection, and Charging (above).
2) Lines sized according to Line Sizing Chart assuming actual
line length plus 10 equivalent feet for fittings losses.
System R-134a Charge Guidelines
System Charge (lbs) by Split Water Cooled
System Model
Ducting for the Evaporator (4000Swc Models)
Cold air exhaust and return (from the evaporator) can be ducted with our front duct
hood up to 50 equivalent feet using
8” diameter insulated ducting, or 100 equivalent
feet with an auxiliary inline fan. Our front duct kit is compatible exclusively with our
4000Swc cooling units.
Before attaching the front duct hoods, remove the front grill (if present) from the
front of cooling unit.
We also offer a remote control panel kit that can be installed remotely (up to 10
feet) from the cooling unit, either inside or outside the cellar, and a bottle probe (10
foot cord) that can be plugged into the cooling unit.