INSTALLING

Continued

NOTICE

You may use this heater as a vented product. If so, you must
always run heater with chimney flue damper open. If running
heater with damper open, non-combustible material above fire-
place opening is not needed. Go to

Installing Damper Clamp

Accessory for Vented Operation, page 13.

Heat Resistant
Material

(A)

Minimum Non Combustible Material Clearances

If Not Using Mantel
Note:

If using a mantel, go to page 11. If not using a mantel, follow the informa-

tion on this page.

You must have non combustible material(s) above the fireplace opening. Non
combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch
thick. With sheet metal, you must have non combustible material behind it. Non
combustible material must extend at least 8" up (for all models). If non combus-
tible material is less than 12", you must install the fireplace hood accessory (24"
and 30" models only). See chart below and Figure 5 for minimum clearances.

IMPORTANT:

If you cannot meet these minimum clearances, you must operate

heater with chimney flue damper open. Go to Installing Damper Clamp Accessory
for Vented Operation,
page 13.

Non-Combustible

Requirements for

Material Distance (A)

Safe Installation

12" or more

Non combustible material okay.

Between 8" and 12"

24" or 30" Models: Install fireplace hood acessory
(GA6050 or GA6052, see

Accessories, page 29).

18" Model: Non combustible material okay.

Less than 8"

Non combustible material must be extended to at
least 8". See

Between 8" and 12", above. If you

cannot extend material, you must operate heater
with flue damper open.

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace