beautypg.com

Risk of breathing, Risk of, Electrical shock – Craftsman 921.166420 User Manual

Page 4: Explosion or fire, Risk of bursting, Specifications, Glossary, Duty cycle

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Important Safety Instructions & Guidelines

Risk of Breathing

Avoid using the air compressor in confined areas. Always have adequate space

(12 inches) on all sides of the air compressor. Also keep children, pets, and others out of

the area of operation. This air compressor does not provide breathable air for anyone or
any auxiliary breathing device. Spraying material will always need to be in another area
away from the air compressor to not allow intake air to damage the air compressor filter.

Risk of

Electrical Shock

Never utilize the air compressor in the rain or wet conditions. Any electrical issues or
repairs should be performed by authorized personnel such as an electrician and should

comply with all national and local electrical codes. The air compressor should also have
the proper three prong grounding plug, correct voltage, and adequate fuse protection.

Risk of

Explosion or Fire

Never operate the compressor near combustible materials, gasoline or solvent vapors.
If spraying flammable materials, locate the air compressor at least 20 feet away from the
spray area. Never operate the air compressor indoors or in a confined area.

Risk of Bursting

Always drain the air compressor tank daily or after each use. If the tank develops a leak,
then replace the air compressor. Never use the air compressor after a leak has been
found or try to make any modifications to the tank. Never modify the air compressor’s
factory settings which control the tank pressure or any other function.

Specifications

Pump..................................................... Oil-Free Direct Drive
Motor............................................................................. 1.5 HP
Bore................................................................................. 2.28"

Stroke.............................................................................. 0.87"
Voltage Single Phase................................................120 VAC

Glossary

CFM:

Cubic feet per minute.

SCFM:

Standard cubic feet per minute; a unit of measure

for air delivery.

PSIG:

Pounds per square inch gauge; a unit of measure

for pressure.

ASME:

American Society of Mechanical Engineers.

California Code:

Unit may comply with California Code

462 (I) (2)/ (M) (2).

Duty Cycle

Minimum Circuit Requirement................................ 15.0 Amps

Air Tank Capacity................................................... 20 Gallons
Cut-in Pressure............................................................120 PSI
Cut-out Pressure......................................................... 150 PSI
SCFM @ 90 PSI.................................................................. 3.8
SCFM @ 40 PSI.................................................................. 5.1

Cut-In Pressure:

The air compressor will automatically

start to refill the tank when the pressure drops
below the prescribed minimum.

Cut-Out Pressure:

The point at which the motor stops

when the tank has reached maximum air
pressure.

Code Certification:

Products that bear one or more of

the following marks: UL, ULc, ETL, CSA, have

been evaluated by CSHA-certified independent
safety laboratories and meet the applicable
Underwriters Laboratories Standards for Safety.

This is a 50% duty cycle air compressor. Do not run the air compressor more than 30 minutes of one hour. Doing so
could damage the air compressor.