Specifications

|

Table 13. Environmental and Safety

200V Models

208V Models

230V Models

Operating Temperature

Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)

Above 1,500 meters: 0°C to 35°C (32°F to 95°F)

Transit/Storage
Temperature

-15°C to 60°C (5°F to 140°F)

Relative Humidity

0–95% noncondensing

Operating Altitude

Up to 3,048 meters (0–10,000 ft) above sea level

Audible Noise

Less than 55 dBA on line/bypass mode (less than 75% load), room temperature

Fan Speed

Low speed: when the load is < 80%

High speed: when the load is >80% or the UPS is in Battery mode

Surge Suppression

ANSI/IEEE C62.41; 1991 Category B3

Safety Conformance

UL 1778 4th Edition;

CSA C22.2, No. 107.3;

IEC/EN 62040-1-1;

IEC/EN 60950-1

UL 1778 4th Edition;

CSA C22.2, No. 107.3

UL 1778 4th Edition;

CSA C22.2, No. 107.3;

IEC/EN 62040-1-1;

IEC/EN 60950-1

Safety Markings

UL, cUL, CE, GS, GOST,

BSMI, S-MARK, KC,

NRCS, C-tick

UL, cUL, VCCI

UL, cUL, CE, GS, GOST,

BSMI, S-MARK, KC,

NRCS, C-tick

EMC (Class A)

IEC/EN 62040-2;

EN 55022/CISPR 22;

ICES-003; CNS14757-2;

AS/NZS 62040.2;

FCC Part 15; KN22;

GB7260.2;

EN 55024/CISPR 24

FCC Part 15, ICES-003,

VCCI

IEC/EN 62040-2;

EN 55022/CISPR 22;

ICES-003; CNS14757-2;

AS/NZS 62040.2;

FCC Part 15; KN22;

GB7260.2;

EN 55024/CISPR 24