Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
O
U T L E T S
— The Rack PDU has four (4) C19 outlets.
P
O W E R
C O R D
— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 32 A plug.
G795N
Electrical
Input connection
IEC-309 32 A (AUS) cord included
Acceptable input voltage
120–250 VAC +6% to -10%
Maximum input current (phase)
32 A
Input frequency
50/60 Hz
Output voltage
120–250 VAC +6% to -10%
Output connections
(4) C19
Maximum output current (outlet)
C19; 16 A
Maximum output current (phase)
32 A
Maximum output current (bank)
16 A
Overcurrent protection (internal)
(2) 20 A, 1-pole breakers
Cord length
3.65 m (12.00 ft)
Physical
Dimensions
(H x W x D)
43.81 x 4.36 x 9.29 cm
(17.25 x 1.72 x 3.66 in)
Shipping dimensions
(H x W x D)
47.80 x 20.80 x 18.00 cm
(18.82 x 8.19 x 7.09 in)
Weight
3.10 kg (6.82 lb)
Shipping weight
4.00 kg (8.80 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety approvals
energysafe Victoria
ROHS
Dell 6T198
EU DIRECTIVE 2002/95/EC–latest revision