Table 1 — condenser unit application, Table 2 — physical data – Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 User Manual
Page 6
Table 1 — Condenser Unit Application
UNIT
50BZ
09BY
006
008
012
014
016
024
006
S
008
S
012
O
S
014
O
S
016
O
S
024
O
S
LEGEND
S — Standard
O — Optional
NOTE: Contact your local representative for use with reciprocating air-cooled chillers and other compressor-bearing unit combinations.
Table 2 — Physical Data
UNIT 09BY
006
008
012
014
016
024
NOMINAL TONS
5
7
1
⁄
2
10
12
15
20
OPERATING WEIGHT (Lb)
267
357
441
471
837
970
REFRIGERANT
R-22
Number of Circuits
1
1
2
2
2
3
Minimum Charge (Lb/Ckt)
6
11
6
6/11
11
11
Optimum Charge (Lb/Ckt)
8.38
14.5
8.38
8.38/14.5
14.5
14.5
Storage Volume Ft
3
/Ckt)
0.31
0.47
0.31
0.31/0.47
0.47
0.47
Holding Charge
Nitrogen Charge
CONDENSER FAN
Belt Drive, Centrifutal
Nominal Airflow (Cfm)
3000
4500
6000
7200
9000
12,000
Cfm Range
2000-4500
3400-6400
4500-7000
6000-7600
6700-9750
7500-11,000
Quantity
2
2
2
2
2
2
Size (in.)
8.8 Ч 8.8
11.0 Ч 11.0
11.0 Ч 11.0
11.0 Ч 11.0
12.4 Ч 12.4
14.0 Ч 14.0
Pulley Size (in.)
5
11
⁄
16
7
5
⁄
8
6
5
⁄
8
6
11
⁄
16
10
13
11
⁄
16
Motor Pulley Range (in.)
4
3
⁄
16
-5
1
⁄
2
4
3
⁄
16
-5
1
⁄
2
4-5
4-5
4
3
⁄
4
-6
5
3
⁄
8
-6
5
⁄
8
Rpm Range
1365-1566
960-1260
1106-1455
1045-1306
840-1050
686-847
Maximum Fan Rpm
1705
1365
1365
1365
1210
955
Belt Quantity...Size
1...A41
1...B46
1...B45
2...A45
2...B88
3...B90
Pulley Center Line Distance (in.)
11.2/12.6
13.6/15.0
13.6/15.0
13.6/15.0
32.6/33.8
30.0/30.7
Fan Shaft (mm)*
20
25
25
25
25
30
Motor Shaft (in.)
7
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
3
⁄
8
Motor Hp...Type
2...TEFC†
3...TEFC
3...TEFC
5...TEFC
5...TEFC
10...TEFC
Motor Frame Size
145T
182T
182T
184T
184T
215T
Maximum Motor Hp
3
5
5
5
5
10
CONDENSER COIL
3
⁄
8
-in. OD Enhanced Copper Tube, Aluminum Fin
Rows...Fins per in.
4...14
5...14
5...14
5...14
4...15
5...15
Face Area (sq ft)
6.33
8.75
10.12
11.45
19.38
19.38
CONNECTIONS
Hot Gas
Quantity
1
1
2
2
2
3
Size (in.)
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
Liquid Line
Quantity
1
1
2
2
2
3
Size (in.)
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
Condensate Drain (in.)
3
⁄
4
FPT
CONTROLS
24-V Control Fan Contactor Provided in Unit
*Metric size.
†TEFC — Totally Enclosed Fan Cooled.
NOTE: Optimum charge is based on 15° F subcooling. Minimum charge is based on 5° F subcooling.
6