Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 User Manual
Page 5

NOTES:
1. Operational clearances are 0 in. on all sides of the unit.
2. Service clearances are 0 in. (minimum) on the top, rear, and front
of the unit. A minimum of 3 ft service clearance is required on the
unit right side, and a 3 ft clearance is recommended on the left
side (2 ft is the minimum). One side of the unit (either right, left, or
rear) should have the following minimum clearance for removal of
the blower shaft:
UNIT
SIZE
APPROX. SHAFT LENGTH
(in.)
006
41.0
008
47.0
012
51.0
014
51.0
016
55.5
024
73.0
Fig. 3 — Base Unit Dimensions (cont)
CORNER WEIGHTS (Lb)
UNIT
SIZE
A
B
C
D
006
55
73
59
42
008
61
89
73
44
012
86
114
93
64
014
107
142
114
78
016
123
159
127
91
024
132
195
158
95
5