Product overview and specifications – Dell Metered PDU LED User Manual
Page 2

2
Dell Metered Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
O
U T L E T S
— The Rack PDU has twelve (12) 5-15 R outlets.
P
O W E R
C O R D
— The Rack PDU has an IEC-320-C20 inlet and can be used with a detachable power cord (not provided).
J519N
Electrical
Input connection
IEC-320-C20
Acceptable input voltage
100–120 VAC
±
10%
Maximum input current (phase)
16 A
Input frequency
50/60 Hz
Input power
1.9 kVA UL and C-UL (derated), PSE
Output voltage
100–120 VAC (Line-to-Neutral)
Output connections
Twelve (12) 5-15 R
Maximum output current (outlet)
5-15 R: 12 A UL and C-UL (derated), PSE
Maximum output current (phase)
16 A UL and C-UL (derated), PSE
Physical
Dimensions
(H x W x D)
85.2 x 5.5 x 4.1 cm
(33.6 x 2.2 x 1.6 in)
Shipping dimensions
(H x W x D)
108.2 x 22.0 x 12.1 cm
(42.6 x 8.65 x 4.75 in)
Weight
2.0 kg (4.5 lb)
Shipping weight
3.2 kg (7.0 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety
UL, C-UL, PSE
EMC
FCC Part 15 Class A, ICES-003 Class A, VCCI-A,
EN 55022 Class A, EN 55024, EN 61000-3-2,
EN 61000-3-3, AS/NZS CISPR 22 Class A,
EU EMC DIRECTIVE 2004/108/EC–latest revision
Environmental
Dell 6T198
EU RoHS DIRECTIVE 2002/95/EC–latest revision