Physical data, Outdoor sound: octave band data—decibels (lw(a)), 50xp – Carrier 13 50XP User Manual
Page 4

4
50XP
OUTDOOR SOUND: OCTAVE BAND DATA—DECIBELS (Lw(A))
Physical data
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated
cooling airflow or the heating airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity
type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
MODEL NO.
50XP
Frequency (Hz)
024
030
036
042
048
060
125
58.8
58.8
60.7
56.7
62.4
63.5
250
63.5
63.5
63.3
62.8
69.9
67.6
500
67.2
67.2
66.8
67.8
71.3
71.8
1000
66.9
66.9
66.5
67.4
73.4
75.5
2000
63.7
63.7
64.2
63.7
70.0
71.0
4000
58.3
58.3
60.3
57.7
66.3
68.1
8000
50.0
50.0
53.0
50.8
60.1
59.9
UNIT SIZE 50XP
024
030
036
042
048
060
NOMINAL CAPACITY (ton)
2
2-1/2
3
3-1/2
4
5
OPERATING WEIGHT (lb)
343
343
366
433
456
492
COMPRESSOR
Scroll
REFRIGERANT (R-410A)
Quantity (lb)
7.3
8.0
9.5
10.7
11.25
13.2
REFRIGERANT METERING DEVICE
(Indoor)
TXV
TXV
TXV
TXV
TXV
TXV
CONDENSER COIL
Rows—Fins/in.
Face Area (sq ft)
2—21
11.95
2—21
12.0
2—21
13.6
2—21
15.4
2—21
17.4
2—21
19.3
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
2350
22
1/8 (825)
2700
22
1/8 (825)
2350
22
1/8 (825)
2800
22
1/8 (825)
3300
22
1/4 (1100)
3300
22
1/4 (1100)
EVAPORATOR COIL
Rows—Fins/in.
Face Area (sq ft)
3—15
3.7
3—15
3.7
4—15
3.7
3—15
4.7
4—15
4.7
4—17
5.7
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (Hp)
800
10 x 10
1/2
1000
10 x 10
1/2
1100
11 x 10
3/4
1400
11 x 10
3/4
1400
11 x 10
3/4
1750
11 x 10
1.0
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto.)
610 ± 15
420 ± 25
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto.)
20 ± 5
45 ± 10
RETURN-AIR FILTERS (in.)*
Throwaway
20 x 20 x 1
20 x 20 x 1
20 x 24 x 1
24 x 30 x 1
24 x 30 x 1
24 x 30 x 1
3 2
5
A2
M
A
N
U
F
A
C
T
U
R
E
R
CE
RT
IFIED
TO ARI
AS
CO
M
P
L
Y
IN
G
W
IT
H
A
RI
STANDARD
21
0
U
N
IT
A
R
Y
AIR
CO
N
D
IT
IO
N
IN
G
EQUIPMENT
50XP