Performance data (cont), Economizer 1-in. filter pressure drop (in. wg), Filter pressure drop (in. wg) – Carrier 13 50XP User Manual
Page 14

14
50XP
Performance data (cont)
ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)
MULTIPLICATION FACTORS
Example: 15.0 kW (at 240v) heater on 208 v
= 15.0 (.75 mult factor)
= 11.25 capacity at 208 v
UNIT50XP
PRESSURE DROP
024-036
0.20
042-060
0.25
HEATER kW
RATING
VOLTAGE
DISTRIBUTION
MULTIPLICATION
FACTOR
240
200
208
230
240
.69
.75
.92
1.00
ELECTRIC HEAT PRESSURE DROP TABLES
Small Cabinet: 024-036
Large Cabinet: 042-060
STATIC
CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
5 kW
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
7.5 kW
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.03
0.05
0.07
0.08
0.09
10 kW
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
0.09
0.10
0.11
15 kW
0.00
0.00
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
STATIC
CFM
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
5 kW
0.00
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
7.5 kW
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
10 kW
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
15 kW
0.00
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
20 kW
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
FILTER PRESSURE DROP (In. wg)
FILTER SIZE
CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
20 X 20 X 1
0.05
0.07
0.08
0.10
0.12
0.13
0.14
0.15
—
—
—
—
—
—
—
—
—
—
—
20 X 24 X 1
—
—
—
—
0.09
0.10
0.11
0.13
0.14
0.15
0.16
—
—
—
—
—
—
—
—
24 X 30 X 1
—
—
—
—
—
—
—
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18