Crestron CHV-TSTAT and CHV-THSTAT

Thermostats

HVAC Related Analog Joins (continued)

Signal Name

Symbol

I/O

Definition

REGULATION_TEMP_F

Both Output

Temperature used for regulation, this is the mean
(averaged) temperature for all sensors declared “use”, in
10ths of degrees

BUILT_IN_TEMP_F

Advanced

Output

Temperature of the built-in sensor, in 10ths of degree,
Note that the values are reported regardless of the
use/OD/omit setting

REM1_TEMP_F

Advanced Output Temperature of remote 1 sensor, in 10ths of degree

Unconnected sensors are reported as 0, Note that the
values are reported regardless of the use/OD/omit
setting

REM2_TEMP_F

Advanced

Output

Temperature of remote 2 sensor, in 10ths of degree
Unconnected sensors are reported as 0, Note that the
values are reported regardless of the use/OD/omit
setting

Indirect Text Joins (Serial)

Signal Name

Symbol

I/O

Definition

MESSAGE

Advanced Input

Used for sending a message to the thermostat Appears
on the “messages” view screen

BUTTON_LABEL_1

Advanced

Input

Provides the soft button label for the first remote function
button (up button, page 1)

BUTTON_LABEL_2

Advanced Input

Provides the soft button label for the second remote
function button (down button, page 1)

BUTTON_LABEL_3

Advanced

Input

Provides the soft button label for the third remote
function button (up button, page 2)

BUTTON_LABEL_4

Advanced Input

Provides the soft button label for the fourth remote
function button (down button, page 2)

Advanced Setup Related Analog Joins

Signal Name

Symbol

I/O

Definition

HEAT_ANTICIPATOR_F

Advanced

Output

Heat anticipator value, 1-6 (refer to page 19)

COOL_ANTICIPATOR_F

Advanced

Output

Cooling anticipator value, 1-6 (refer to page 19)

AUTO_MODE_DEADBAND_F

Advanced Output Auto mode deadband value, 2-6 degrees (refer to page

19)

HP_BALANCE_PT_F

Advanced

Output

Heat pump balance point, 0-90˚F (refer to page 19)

AUX_BALANCE_PT_F

Advanced

Output

Aux balance point, 0-90˚F (refer to page 19)

LCD_CONTRAST_F

Advanced

Output

LCD contrast value, 1-10

TEMP_DISP_OFFSET_F

Advanced Output Offset to be added to measured temperature value to

correct display to user preference, -6 - +6 degrees

Setup Related Digital Joins

Signal Name

Symbol

I/O

Definition

HEAT_COOL SYS_F

Advanced Output Asserted when the system is heat/cool type (as opposed

to heat pump)

HEATPUMP_SYS_F

Advanced

Output

Asserted when system type is heat pump

Operations and Installation Guide – DOC. 8163B Thermostats:

CHV-TSTAT and CHV-THSTAT

35