Amico NFPA Triplex SCD Modular Stack Mount User Manual
Page 15
www.amico.com 13
3.
Statement declaring that the MGEM has no fiduciary interest in the verifier and that the verifier is
not an agent or representative of the MGEM.
4.
Statement declaring that the installing contractor has no fiduciary interest in the verifier and that
the verifier has no fiduciary interest in the contractor.
C. Pre-approval
1.
Written preapproval is required for equipment not exactly matching specifications. Submit the
information required under Submittals above, attaching a cover letter stating the exact areas of
deviation.
2.
A request for preapproval of equipment must be received by the Engineer no less than three days
(72 hours) prior to bid.
QUALITY ASSURANCE
A.
Regulatory Requirements
1.
Electrical Control systems and Medical Gas Alarms are to be UL listed as assemblies with label
affixed.
2.
Medical air, instrument air, medical vacuum and WAGD controls are to be wired in accordance with NEC.
3.
All air purification components shall be in compliance with CAGI performance verification as per ISO
8573.1
standards.
4.
MGEM will include with submittals an affidavit attesting to compliance with all relevant paragraphs
of NFPA 99 most recent edition.
5.
MGEM personnel assembling medical air, instrument air, vacuum and WAGD plant shall meet the
latest edition of NFPA 99 “Qualification of Installers” section and hold medical gas endorsements as
under ASSE 6010.
6.
The Contractor shall furnish documentation demonstrating that all installed piping materials were
purchased cleaned and complied with the requirements of NFPA 99 5.1.10.1 and 5.1.10.2.
7.
The Contractor shall furnish copies of ASSE 6010 qualifications for all workers installing medical gas piping.
B.
Installation and Start-up
1.
The MGEM will provide authorized representatives to review installation and perform
initial start-up of the system.
C. Warranty
1.
Warranty will be expressly complete, include all components of the system and be the responsibility
of the MGEM for record only. Warranties limiting the responsibility of the MGEM for any system
component for which pass through the MGEM to another manufacturer are not acceptable.
2.
All source medical gas components shall be warranted by the MGEM of record for a minimum of 30
months from date of shipment.