beautypg.com

Amico CSA Triplex SCD Modular Stack Mount User Manual

Page 14

background image

Amico Source Equipment

3.

Warranties shall include on site repairs including travel, labor and parts.

4.

Shipping and installation costs after the first 12 months will be borne by the customer.

D. Verification:

1.

Medical Gas Contractor shall deliver to the owner a complete system certification.

PART 2 - PRODUCTS

QUALIFICATION OF MANUFACTURER(S)

A.

One manufacturer shall supply all of the medical gas systems equipment, including the sources of supply.

This supplier shall have a product specialist available to periodically check with the Project

Coordinator during initial installation of the pipeline systems equipment. The equipment supplier’s

representative shall train the hospital personnel in the use of the piping system and related equipment in

operation with those systems.

B.

The MGEM shall have a product specialist available to periodically check with the Contractor during

installation of the pipeline systems equipment. MGEM shall provide service support to the hospital after

turnover. Demonstrate factory trained service technician is available within 400 kilometers of facility.

C.

Approved MGEM: Piping Systems Components and Medical Gas Alarms;

1.

Amico Corporation.

2.

Alternate by _____________ with pre approval.

D.

MGEM shall have a minimum of 5 years of experience manufacturing medical air and vacuum systems.

E.

Written Pre-approval is required for all equipment from other manufacturers.

MEDICAL AIR COMPRESSOR SYSTEMS

1.

Provide a complete medical air source, complying with all relevant requirements of CAN/CSA

Standards and supplying medical air continuously for the life of the equipment. The unit shall be

manufactured by Amico or preapproved equal.

2.

All components are at least duplexed and valved to allow servicing to any components devoid of

interruption of air supply of the facility.

3.

System is sized so each filter can meet 100% of the peak calculated demand.

4.

Furnish a complete plant consisting of at least three (3) compressors, receiver, air treatment system

and controls capable of providing scheduled capacity with two units out of service. A medical air

system may have two compressors if the facility requires less than 570 L/min at 345 kPa (20 SCFM at

50 PSI) flow rate.

5.

System is modular or field separable, allowing for ease of shipment and handling on site. System is

completely factory assembled, requiring only interconnection between modules on site. Systems

requiring site assembly other than interconnection are not acceptable (remounting of components

removed for shipping is permitted).

12