beautypg.com

Shr series woodburning fireplace, Installing the chimney system, Installing the firestop spacer in the ceiling hole – CFM Corporation SHR36 User Manual

Page 12: Proper firestop spacer installation

background image

12

SHR Series Woodburning Fireplace

20001384

Installing the Chimney System

Start by attaching the first chimney section to the collar
on top of the fireplace.
Install the pipe as pictured in Figure 19. When you
get a good lock, you will hear the pipe clearly snap
together. Once sections are snap-locked in place, it is
extremely difficult to get them apart. Make sure the
pipe is firmly snapped and locked together as each
pipe section is mounted.
When installing elbows, only outer pipe will snap- lock.
Middle pipes simply slide into position. Be sure to
always attach straps on upper elbow to a structural
framing member. (Fig. 20)
Continue installing the pipe as required until pipe is
installed up through the ceiling. At this point, you must
install a firestop spacer.

FP270/271

CR Series

2/19/99 djt

ELBOW STRAP

ANGLED STRAP

Fig. 20 Attach straps to a structural framing member.

FP270/271

Support Structure

Elbow Strap

(must be tight)

Ceiling

Hole

Framing

Angle Firestop

Chimney Support

Strap

(must be tight)

UP

FP558SHR

snap lock

5/11/99 djt

FP558SHR

Fig. 19 Install pipe, listening for the snap-lock to fasten.

Inner Pipe Section

Hem

Lance

Pipe

Rim

Pipe

Rim

FP710a

SHR OUTSIDE AIR LEVER

WOOD FIREPLACES

10/21/99

Closed

Open

Fig. 18 Outside air operation.

FP710a

Installing the Firestop Spacer

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly
and required for safety.
Nail the firestop spacer (at each corner) to the framing
members of the ceiling hole. Note: A firestop spacer is
not required at the roof.
Hole sizes listed in Figure 14 for angled firestop spac-
ers provide minimum required air space to chimney
pipe for ceiling thickness up to eight (8) inches. When
combined thickness of ceiling material, ceiling joists and
flooring material exceeds eight (8) inches, adjustments
must be made in framing to assure that minimum air
spaces to chimney are maintained.

Proper Firestop Spacer Installation

Figure 21 shows different installation procedures for
both an area that is an attic and an area that is not an
attic.
If the area above the ceiling is not an attic, position the
firestop spacer with the flange on the ceiling side and
the angled portion extending up into the hole.
If the area above the ceiling is an attic, position the
firestop spacer with the flange on the top of the framed
hole and the angled portion extending down into the
hole.
Firestop spacers are not available for, nor are they
required on, vertical walls.
The chimney components (CF11) used on the SHR
series fireplaces have been tested and approved with
the area where the outer pipe slides through the firestop
spacer sealed with a noncombustible caulk if desired,
or left completely open with no sealant. This sealing
only applies to the SHR series fireplace.

This manual is related to the following products: