To insure proper adhesion of the pressure sensitive plastic
cell numerals, and polarity markings supplied with your
GNB
®
Flooded Classic Battery, the following procedure
should be followed:
1. Numerals and polarity markings should not be applied
until after the cells have been installed on the rack. It is
recommended that they be applied to jar surfaces only,
and not to cell covers or rack rails.
2. Clean the plastic jar surface, in the area where the
numeral is to be located, by using a cloth dampened
with a washing soda solution. Immediately dry the area
using a soft dry cloth to remove residual washing soda.
CAUTION!! Do not use any solvent type materials as
they may cause damage to the plastic jar material.
3. It is a general practice to designate the positive terminal
cell as #1 with succeeding cells in series in ascending
order.
4. Numerals are shipped mounted on a plastic backing
strip. They are easily removed by peeling back the plas-
tic strip. Keep finger contact with adhesive backing on
numeral to a minimum.
5. Locate and place numeral on side of jar, being careful
that there is no conflict with electrolyte level lines or side
rails of SEISMIC TYPE RACKS. For clean appearance,
exercise care in numeral placement so that all the
numerals are in the same relative position on each cell.
Install polarity markings on the appropriate cells in the
same manner.
6. Following application of cell numerals and polarity mark-
ings, use a dry cloth to rub entire surface of each label
to insure proper surface contact.
Note: Design and/or specifications subject to change
without notice. If questions arise, contact your local
sales representative for clarification.
7
STATIONARY BATTERY PLASTIC CELL NUMERAL APPLICATION
TYPICAL BATTERY NAMEPLATE
NO. OF CELLS
TYPE
SERIAL NO.
CAPACITY
AMPERE HRS. AT
HR. RATE
SPECIFIC GRAVITY
GNB Industrial Power, Aurora, IL 60504
®