Q-SERIES DI HEATER OPERATION / MAINTENANCE MANUAL

PAGE 21

Name

Address Type Data Bytes Perm

Value

Alarm Status

003075

Coil Bool

1

R

0-1

Alarm Pressure

003081

Coil Bool

1

R

0-1

Alarm Pressure Status

400641

Reg Short

2

R

1-4

Alarm Liquid Leak

003082

Coil Bool

1

R

0-1

Alarm Liquid Level

003084

Coil Bool

1

R

0-1

Alarm Liquid Level Status

400644

Reg Short

2

R

1-4

Alarm Over Temp

003083

Coil Bool

1

R

0-1

Alarm Thermocouple

003085

Coil Bool

1

R

0-1

Flow Range

003111

Coil Bool

1

RW

0-1

Percent Power

400671

Reg Short

2

R

0-100(%)

Process Temperature

400778

Reg Short

2

R

0-120(°C)

Remote heater Power

003112

Coil Bool

1

RW

0-1

Remote Mode

003113

Coil Bool

1

R

0-1

Remote Set Point

400786

Reg Short

2

RW 10-95(°C)

Table 5-2: Modbus Address Mapping

For example:

To enable the heating of water, a write request must be sent to the

address for the

“Remote Heater Power” coil with a value of 1.

To disable the heating of water, a write request must be sent to the

address for the

“Remote Heater Power” coil with a value of 0.

To monitor the temperature set point, a read request must be sent to

the address for the

“Remote Set Point” register.

To adjust the temperature set point, a write request must be sent to

the address for the

“Remote Set Point” register with a value between

15 and 95.